HeatTimer HWR Platinum Hydronic Heating Control with System and Outdoor Sensors and Necessary Relays for BACnet IP/MSTP Communication Package 926795-BAC
HeatTimer HWR Platinum Hydronic Heating Control with System and Outdoor Sensors and Necessary Relays for BACnet IP/MSTP Communication Package 926795-BAC
The HWR Platinum is an outdoor reset boiler or motorized valve heating control. The HWR Platinum will start and stop the boiler and modulate a motorized valve, to vary the system water temperature in a buildings radiation in accordance with changes in outside temperature based on the Outdoor Reset Ratio settings. Unlike other outdoor reset controls that uses the space temperature to shutdown the system, the HWR Platinum monitors the space temperature over a time period and uses that data to help reduce temperature fluctuation in the building. In addition to building heating, the HWR platinum offer Domestic Hot Water Priority. Add to that its capability of controlling the domestic hot water pump.
Features & Benefits
Adjustable Outdoor Temperature Cutoff
Adjustable Reset Ratios, Offset, Minimum and Maximum Water Temperatures
Anticipatory Space Feedback Capability
4 Programmable Day/Night Adjustments Per Day
Multiple Setback Schedules
Optimum Variable Boost [Morning Warm-Up]
Built-in Domestic Hot Water Priority Option
Auxiliary Output that can Control Other Equipment Based on a Separate Built-in Programmable 4 Separate On/Off Schedule Settings Per Day [HWR Platinum only]